[ Up ] [ AL 60 ] [ CI – CABLE IDENTIFIER ] [ Model 510 Cable Locator ] [ FERROLUX ] [ PIL 8 ] [ PVS 100 ] [ MMG 5 ] [ MMG 10 ] [ ESG 80 ] [ MVG 5 ]
PVS
100
The system consists of two
identical devices, one of which is used as a base
station and is connected to a known reference phase. The
second device (the mobile unit) can be connected
anywhere in the network. The phasing can be determined
across various voltage levels by comparing the angle of
the phase currently being tested with that of the
reference phase. Automatic comparison with a direct
indication of the phase assignment takes place by
synchronizing the two devices via a mobile connection,
using GPS as a highly accurate time base. If there are
one or more transformers between the base station and
the test point, the effect of the vector groups and the
associated phase shifts (multiples of 30°) can be easily
taken into account by entering appropriate correction
values. Special operating modes allow the system to be
used even when there is no GPS or cellular connection.
To do this, the mobile unit can either be synchronized
before the test to an available low voltage supply that
remains connected, or the recorded test readings are
synchronized via an existing mobile connection after the
test. The PVS 100 can be used anywhere thanks to its
built-in rechargeable battery. The system is directly
connected to the test object at network voltages up to
400 V. At higher voltages, up to 120 kV, the test is
performed using a high voltage sensor which communicates
with the PVS 100 via bidirectional wireless
communication. The test status and the phase indication
are signaled using a visual display on the sensor.
|